CDU Installation Guide Page 28
Cooling Distribution Unit
OPERATION (continued)
6.2 Controller Menu Summary
All items shown on this background are available to all personnel with no requirement for an access
code.
All items shown on this background are only available to service engineers only with the correct access
code.
All items shown on this background are only available to factory authorized personnel with the correct
‘Engineering’ access code.
Controller Menu Structure (software version 1.5 shown)
Waiting for service msg. (press button on mother board to attach)
No. of RDHx 1 to 6 (set as required)
Units* SI or Imperial
Daylight Saving Hours Europe, Manual, No DST or N. America
Date Format dd/mm/yy or mm/dd/yy
Date & time dd/mm/yy hh:mm:ss (24 hour clock)
Reset parameters to defaults
engineering code – on request from manufacturer
Status (screen 3) - read only information
Standby / Online / Fault / Shutdown / Manual
Heat exchanger
(see page 27 for
explanation)
Valve no -- O/P --- % Act --- %
Secondary SP --.- °C(°F) Act --.- °C(°F)
Room sensor Temp --.- °C(°F) RH --.- %
DP o/r DP --.- °C(°F)
--.- (temperature) and --.- (relative humidity)
PS1 --.-- Bar (PSI) (pump suction pressure)
PS2 --.-- Bar (PSI) (pump discharge pressure)
DP --.-- Bar (PSI) (pump differential pressure)
PS3 --.-- Bar (PSI) (filter inlet pressure)
PS4 --.-- Bar (PSI) (filter outlet pressure)
DP --.-- Bar (PSI) (filter differential pressure)
T2a --.- °C(°F) (water supply temperature to RDHx’s)
T2b --.- °C(°F) (water supply temperature to RDHx’s)
Ave --.- °C(°F) (average T2a & T2b)
--.- °C(°F) (incoming chilled water temperature)
--- L/M (USgpm) (chilled water flow – not accurate below 20L/M (5USgpm))
Hours (total run time in hours of pumps 1 & 2)
Hours (total run time in hours of valve 1 - at 25,50,75 & 100% positions)
Hours (total run time in hours of valve 2 - at 25,50,75 & 100% positions)
3-12-1 Digital Inputs & Outputs (see page 27 for explanation)
3-12-2 Analogue Inputs
3-12-3 Resistive Inputs
3-12-4 Universal Inputs
3-12-5 Analogue Outputs
(Raw data for factory information only)
(Raw input data - for
factory information only)
* Note: If the ‘units’ are changed during CDU operation, any parameters that have
been previously adjusted, will revert to default values in the new chosen ‘units’.